Energy Edge Solutions

Using Power Factor Correction and Transient Voltage Surge Suppression to Reduce Energy Costs

By Robert Holdsworth
President of Energy Edge Solutions Corp.

Today’s energy conscious climate has motivated many to do what they can to become
more efficient and conserve energy and money. Unfortunately this same climate has
prompted others to take advantage of unsuspecting consumers’ wishes to save energy and
reduce expenses.

Companies that tout power factor improvement (kVAR correction) and transient voltage
suppression are a good example of this bad trend. Lately we are seeing more and more of
these companies cropping up and feel it is time to set the record straight.

First, transient voltage surge suppression (TVSS) plays a valuable role in improving
power quality to protect sensitive equipment inside a facility. However, TVSS does
not save energy. TVSS’s are only active a tiny fraction of a second to protect against
voltage surges which only last for less than a millisecond. To actually reduce energy
consumption the TVSS would need to actually cut power consumption for an extended
period of time which is not what they are designed to do. Again, TVSS is important to
protect sensitive electrical equipment but buyers should avoid vendors promising, or even
guaranteeing, that they will reduce energy consumption.

Now what about vendors who claim that improving power factor will save 15% or 20%
or 30% of energy consumption and corresponding cost? This one is a little trickier.

For residential applications, power factor does nothing to save energy because the
typical home already has an average power factor of about 0.97 which is almost the
perfect power factor of 1 or unity. In addition, the device (called a capacitor) is placed
at the main circuit breaker. According to IEEE 5.5.3.3 capacitors must be situated at or
near the respective inductive loads to reduce power system losses by reducing heat and
distribution losses known as I2R losses.

So what about commercial and industrial facilities using power factor correction to
reduce energy costs? It is perfectly appropriate for a company that is incurring penalties
or a kVA billing structure from the utility company to improve the facility’s overall
power factor by employing a capacitor bank at the main service entrance or individual
capacitors at or near the respective motor loads. Doing so will eliminate the power
factor penalties and/or reduce the kVA demand charges on the utility bill which can save
significant money and provide a significant ROI on the investment.

But what about power factor correction reducing kWh consumption? IEEE also tells us
that I2R losses only account for 2 to 5% of the total load in a facility. Simple math tells
us that it would be against the laws of physics to get the 15% to 30% energy reduction
claimed by some vendors. Think about it. Even if your facility had 5% distribution

losses and you could correct 100% of the problem via power factor correction at every
load (which can’t be done) you would still only save 5% at the most. No where near the
claims of some capacitor vendors and manufacturers.

All that said, power factor correction when done properly will eliminate utility penalties
and kVA demand charges, improve facility power quality, increase electrical system
capacity, and save a little energy when applied to the appropriate motor loads.

So make an investment in transient voltage surge suppression and power factor correction
when appropriate and necessary. But caveat emptor!

Enhanced by Zemanta
  • http://www.googleredirectfix.com/ Browser Redirect Virus

    Gems form the internet…

    [...]very few websites that happen to be detailed below, from our point of view are undoubtedly well worth checking out[...]……